Interface hook-up data sheet for Draupner

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main440
3p+e
6063/80NoS63ASocket:
GHG 534 1407 V5076 7h
Plug:
GHG 534 2407 V5076 7h
Draupner-S
M10, C10
Main440
3p+e
6063/80NoS63Socket:
GHG 534 1407 V5076 7h
Plug:
GHG 534 2407 V5076 7h
Draupner-E
C30, M30, M31, M32, M33, W30
Main440
3p+e
6032NoS32Socket:
GHG 532 4407 V0 7h
Plug:
GHG 532 7407 V0 7h
Draupner-S
M10, C10
Main230
2p+e
6016NoS16Socket:
GHG 5114306R0001 6H
Plug:
GHG 5117306R0001 6H
Draupner-S
M10, M11, C10
Main440
3p+e
6032NoS32Socket:
GHG 532 4407 V0 7h
Plug:
GHG 532 7407 V0 7h
Draupner-E
C30, M30, M31, M32, M33, W30
Main230
2p+e
6016NoS16Socket:
GHG 5114306R0001 6H
Plug:
GHG 5117306R0001 6H
Draupner-E
C30, M30, M31, M32, M33, W30

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Gas
Other
Loss Of Pressure
Fire
ESD Battery System

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
TelephoneAudioSocket: STAHL 8570/11-410 10h (green) 1&2 = sign., 3= scr., 4= armeringPlug: STAHL 8570/12-410 10h (green) 1&2 = sign., 3= scr., 4= armering
PAAudio, 100V lineSocket: STAHL 8570/11-404 4h (yellow) 1&2 = sign., 3= scr., 4= armeringPlug: STAHL 8570/12-404 4h (yellow) 1&2 = sign., 3= scr., 4= armering

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Plant Air
Instrument Air
Seawater
Drain
Other
Sprinkler
Freshwater

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
Draupner S (1150-73-MA-100)50 tonn / 25m50 tonn / 20m44,5 tonn / 15m
Draupner E (1150-73-MA-800)39,8 tonn / 9m32,1 tonn / 9m25,8 tonn / 9m

* Significant waveheight [max. load / max. radius]