Interface hook-up data sheet for Gullfaks A

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main440
3p+e
60125NoS125Socket:
GHG 515 4507 V0 7h
Plug:
GHG 515 7507 V0 7h
M16, M17, M35 and D31
Main230
2p+e
6016NoS16Socket:
STAHL 8570/11-306
(blue) 6h
Plug:
Stahl 8570/12-306
(blue) 6h
Socket outlets all over the platform
Main440
3p+e
6063NoS63Socket:
STAHL 8579/31-507
(black) 7h
Plug:
STAHL 8579/12-507
(black) 7h
Welding socket outlets all over the platform

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
FireDI - NO
(Digital Input- Normaly open)
Socket outlet:
CEAG GHG 511 4906
R0001 6h KU, pin 1,2
Plug
CEAG GHG 591 2201
R0002 6h pin 1, 2
D31NV, D31SV, L139, M13DN, M16/17 BOP, M16/17S, M18DN, M18T, M21DS, M21TS, M24MS, M35TN, M35TØ, M35TS
GasDI - NO
(Digital Input- Normaly open)
Socket outlet:
CEAG GHG 511 4906
R0001 6h KU, pin 4,5
Plug
CEAG GHG 591 2201
R0002 6h pin 4, 5
D31NV, D31SV, L139, M13DN, M16/17 BOP, M16/17S, M18DN, M18T, M21DS, M21TS, M24MS, M35TN, M35TØ, M35TS
ESD Battery System
Loss Of PressureDI - NO
(Digital Input- Normaly open)
Socket outlet:
CEAG GHG 511 4906
R0001 6h KU, pin 7,8
Plug
CEAG GHG 591 2201
R0002 6h pin 7,8
D31NV, D31SV, L139, M13DN, M16/17 BOP, M16/17S, M18DN, M18T, M21DS, M21TS, M24MS, M35TN, M35TØ, M35TS
OtherDI - NO
(Digital Input- Normaly open)
Socket outlet:
CEAG GHG 511 4906
R0001 6h KU, pin 10, 11
Plug
CEAG GHG 591 2201
R0002 6h pin 10, 11
D31NV, D31SV, L139, M13DN, M16/17 BOP, M16/17S, M18DN, M18T, M21DS, M21TS, M24MS, M35TN, M35TØ, M35TS

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
PASocket:
STAHL 8570/11-404
(yellow) 4h
Plug:
STAHL 8570/12-404
(yellow) 4h
TelephoneSocket:
STAHL 8570/11-402
(green) 2h
Plug:
STAHL 8570/12-402
(green) 2h

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Plant Air
Sprinkler
Freshwater
Other
Instrument Air
Seawater
Drain

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
Kran 142 t. / 20 meter42 t. / 20 meter38 t. / 20 meter (E)
Kran 3Kun lettløftKun lettløftKun lettløft
Kran 430 t. / 20 meter30 t. / 20 meter29 t. / 20 meter
Kran 242 t. / 20 meter42 t. / 20 meter38 t. / 20 meter (E)

* Significant waveheight [max. load / max. radius]

Comments

I TABELLEN VISES MAKS. LØFTEKAPASITET FOR LØFT MED STORBLOKK FRA FORSYNINGSSKIP (tonn) I FORHOLD TIL SIGNIFIKANT BØLGEHØYDE (meter).

Additional information

Eksempel på fremføring av instrumentsignal i kontainer GFA:
Kontainer skal alltid bestykkes med 4 stk 2K endemotstander og 4 kabelpar, selv om ikke kontainer har funksjonalitet for alle signaltyper.