Interface hook-up data sheet for Gullfaks C

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Emg440
3p+e
6063NoS63Socket:
STAHL 8579/31-507
(black) 7h
Plug:
STAHL 8579/12-507
(black) 7h
Four sokcet outlets for the wire-line unit in the M16/17 area
Emg440
3p+e
60125NoS125Socket:
GHG 515 4507 V0 7h
Plug:
GHG 515 7507 V0 7h
Two socket outlets for wire-line operations. Located i M16 and M17.
D31T North and South
Main440
3p+e
60125NoS125Socket:
GHG 515 4507 V0 7h
Plug:
GHG 515 7507 V0 7h
C11 one socket outlet,
M13M North one socket outlet,
M16D North one socket outlet,
M24M South one socket outlet,
D11T one socket outlet,
D31T North and South
Main440
3p+e
6063NoS63Socket:
STAHL 8579/31-507
(black) 7h
Plug:
STAHL 8579/12-507
(black) 7h
Welding socket outlets all over the plattform
Main230
2p+e
6016NoS16Socket:
STAHL 8570/11-306
(blue) 6h
Plug:
STAHL 8570/12-306
(blue) 6h
Socket outlets all over the platform

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Loss Of PressureDI - NO
(Digital Input- Normaly open)
Socket outlet:
CEAG GHG 511 4906
R0001 6h KU, pin 7, 8
Plug
CEAG GHG 591 2201
R0002 6h pin 7, 8
L119, M21S, M21N, M24N, M16BOP, M17BOP, D31S, D31N
GasDI - NO
(Digital Input- Normaly open)
Socket outlet:
CEAG GHG 511 4906
R0001 6h KU, pin 4, 5
Plug
CEAG GHG 591 2201
R0002 6h pin 4, 5
L119, M21S, M21N, M24N, M16BOP, M17BOP, D31S, D31N
FireDI - NO
(Digital Input- Normaly open)
Socket outlet:
CEAG GHG 511 4906
R0001 6h KU, pin 1, 2
Plug
CEAG GHG 591 2201
R0002 6h pin 1, 2
L119, M21S, M21N, M24N, M16BOP, M17BOP, D31S, D31N
OtherDI - NO
(Digital Input- Normaly open)
Socket outlet:
CEAG GHG 511 4906
R0001 6h KU, pin 10, 11
Plug
CEAG GHG 591 2201
R0002 6h pin 10, 11
L119, M21S, M21N, M24N, M16BOP, M17BOP, D31S, D31N
ESD Battery System

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
PASTAHL 8570/11-404 4h
(yellow)
STAHL 8570/12-404 4h
(yellow)
TelephoneSTAHL 8570/11-402 2h
(green)
STAHL 8570/12-402 2h
(green)

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Sprinkler
Freshwater
Drain
Other
Plant Air
Instrument Air
Seawater

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
Kran 350 t./16 meter45 t./16 meter37 t./16 meter
Kran 430 t./23,5 meter28,5 t./23,5 meter23,5 t./23,5 meter
Kran 150 t./16 meter45 t./16 meter37 t./16 meter
Kran 239,5 t./19 meter33,5 t./19 meter27 t./19 meter

* Significant waveheight [max. load / max. radius]

Comments

I TABELLEN VISES MAKS. LØFTEKAPASITET FOR LØFT MED STORBLOKK FRA FORSYNINGSSKIP (tonn) I FORHOLD TIL SIGNIFIKANT BØLGEHØYDE (meter).

Additional information


Eksempel på fremføring av instrumentsignal i kontainer GFC:
Kontainer skal alltid bestykkes med 4 stk 2K endemotstander og 4 kabelpar, selv om ikke kontainer har funksjonalitet for alle signaltyper.