Power * | Volt [V] | Frequency [Hz] | Phase Current [A] | Neutral Loaded [Yes/No] | System earth ** | Short circuit level min [kA] | Short circuit level max [kA] | Distribution protection fuse [A] | Distribution protection earth fault [mA] | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Main | 230 | 50 | 16 | Yes | S | 10 | 16 | Stikk. / Socket: CEAG: GHG 511 4306 V000 (blue) 6h 2P + PE | Støpsel / Plug : CEAG: GHG 543 2306 V0 (blue) 6h 2P + PE | Bare for lys og mindre oppvarmingsformål / Only for lighting and minor heating purpose | ||
Main | 380 | 50 | 125 | Yes | S | 50 | 125 | Stikk. / Socket: ABB: GHG 535 1505 V0 (black) 6h 3P + N + PE | Støpsel / Plug : ABB: GHG 535 2505 V0 (black) 6h 3P + N + PE | Maks / Max 65 kW Bare tilgjengelig ved ROV stasjon nord og syd. Mulighet for tilkopling må avtales spesielt i hvert enkelt tilfelle. / Only available at ROV station north and south. Possibility for connection to be arranged in every particularly case. | ||
Main | 380 | 50 | 63 | Yes | S | 50 | 63 | Stikk. / Socket: ABB: GHG 533 1406 V0 (red) 6h 3P + PE | Støpsel / Plug : ABB: GHG 534 2406 V0000 (red) 6h 3P + PE | Maks / Max 33 kW |
*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power
**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
Loss Of Pressure | Stikk. / Socket: ABB: GHG 542 3300 V0 (violet) | Støpsel / Plug : ABB: GHG 542 2300 V0 (violet) | ||
Fire | Stikk. / Socket: ABB: GHG 542 3300 V0 (violet) | Støpsel / Plug : ABB: GHG 542 2300 V0 (violet) | ||
Other | Tilkopling i koplingsboks / Connection in junction box | |||
ESD Battery System | Stikk. / Socket: ABB: GHG 542 3300 V0 (violet) | Støpsel / Plug : ABB: GHG 542 2300 V0 (violet) | ||
Gas | Stikk. / Socket: ABB: GHG 542 3300 V0 (violet) | Støpsel / Plug : ABB: GHG 542 2300 V0 (violet) |
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
PA | Tilkopling i koplingsboks / Connection in junction box | |||
Telephone | Tilkopling i koplingsboks / Connection in junction box |
Function | Pressure [bar] | Amount/Flow [max capacity] | Connection - type | Connection - diameter | Connection - material | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|
Plant Air | 7,0 | |||||
Instrument Air | 6,5 | |||||
Seawater | 10,5 | |||||
Freshwater | 14 (cellar deck) | |||||
Drain | ||||||
Sprinkler | 10,5 | |||||
Other |
No entries to show.
KORTSLUTNINGSNIVÅ
Verdiene vil være ved kortslutning i selve tavlen.
Kortslutningsnivået i/ved tavlen i det midlertidige utstyret vil være lavere.
Ved beregning av kortslutningsnivå kan følgende parametre brukes:
* Fra installasjonens hovedtavle og via fast opplagt kabel til stikkontakt/tilkoplingspunkt for midlertidig utstyr 3x25mm2 - 50 m.
* Fra installasjonens stikkontakt/tilkoplingspunkt for det midlertidige utstyret og via bevegelig kabel til utstyret 3 x 16mm2 -35 m.
SHORT CIRCUIT LEVEL
Values reflect short circuit level inside the switchboard
Regarding switchboard for temporary equipment the short circuit level inside or at the switchboard will be lower
When calculating the level of the short circuit following parameters can be used:
* From the facilitys main switchboard and via fixed cabling to the socked/connection point for temporary equipment; 3x25mm2 - 50 m.
* From the facilitys socked/connection point for temporary equipment and via flexible cables to the equipment; 3 x 16mm2 - 35 m.