Interface hook-up data sheet for Johan Castberg

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main6905063NoR63STAHL 8579/31-405 3P+PESTAHL 8579/12-405AA700, AV100, AQ200, AR300, AW320, AP600, AP800
Main40050125YesS125STAHL 8581/31-506-S010 3P+N+PESTAHL 8579/12-506AA700, AV100, AQ200, AR300, AW320, AP600, AP800
Main4005063YesS63STAHL 8579/31-506-S001 3P+N+PESTAHL 8579/12-506AA700, AV100, AQ200, AR300, AW320, AP600, AP800
Main4005016NoR16STAHL 8570-11-306 2P+PESTAHL 8570/12-306AT130, AT410, AT420, AT430, AT440, AT510, AT520
Main2305016NoI16STAHL 8570/11-306 2P+PESTAHL 8570/12-306AA700, AV100, AQ200, AR300, AW320, AP600, AP800
UPS2305016NoI16STAHL 8570/11-306 2P+PESTAHL 8570/12-306AA700, AW320
Emg40050125YesS125STAHL 8581/31-506-S010 3P+N+PESTAHL 8579/12-506AA700, AW320
Emg4005063YesS63STAHL 8579/31-506-S001 3P+N+PESTAHL 8579/12-506AA700, AW320

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
FireDigital Input, Loop Supervised, 2 wire, SOE, SIL 1-3, Powered from SAS, Non IS.
Normally open contact (open = no alarm, closed = alarm).
Relay to be normally de-energized
22Kohm in parallel and 1,8Kohm in series
Socket:
GHG 511 4906 R3001
Pin 1, 2
Plug:
GHG 591 2201 R0002
Pin 1, 2
AV100, AQ200, AR300, AW320, AP600, AP800
GasDigital Input, Loop Supervised, 2 wire, SOE, SIL 1-3, Powered from SAS, Non IS.
Normally open contact (open = no alarm, closed = alarm).
Relay to be normally de-energized
22Kohm in parallel and 1,8Kohm in series
Socket:
GHG 511 4906 R3001
Pin 4, 5
Plug:
GHG 591 2201 R0002
Pin 4, 5
AV100, AQ200, AR300, AW320, AP600, AP800
Loss Of PressureDigital Input, Loop Supervised, 2 wire, SOE, SIL 1-3, Powered from SAS, Non IS.
Normally open contact (open = no alarm, closed = alarm).
Relay to be normally de-energized
22Kohm in parallel and 1,8Kohm in series
Socket:
GHG 511 4906 R3001
Pin 7, 8
Plug:
GHG 591 2201 R0002
Pin 7, 8
AV100, AQ200, AR300, AW320, AP600, AP800
OtherDigital Input, Loop Supervised, 2 wire, SOE, SIL 1-3, Powered from SAS, Non IS.
Normally open contact (open = no alarm, closed = alarm).
Relay to be normally de-energized
22Kohm in parallel and 1,8Kohm in series
Socket:
GHG 511 4906 R3001
Pin 10, 11
Plug:
GHG 591 2201 R0002
Pin 10, 11
AV100, AQ200, AR300, AW320, AP600, AP800
ESD Battery SystemDigital Output, Loop Supervised, 24VDC, 2 wire, ≤600mA, SIL 1-3, Powered from SAS, Non IS.
Normally open contact (open = shutdown, closed = no shutdown).
Relay to be normally energized
Junctionbox
STAHL 8150/1-0236-0176-150-3311
Wire in junctionbox
X1:1
X1:2
AV100, AQ200, AR300, AW320, AP600, AP800

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Network (Fiber)Pro beam Jr, 4 FibresPro beam Jr, 4 FibresAV100, AR300, AW320
PAAudio, 100V lineSTAHL 8570/11-404 (Yellow)STAHL 8570/12-404 (Yellow)AV100, AR300, AW320
TelephoneNANANANA

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Other
Drain
Freshwater
Seawater
Sprinkler
Instrument AirNA
Plant Air8,5BarAll utility stations

Lifting capacity offshore cranes

No entries to show.