Power * | Volt [V] | Frequency [Hz] | Phase Current [A] | Neutral Loaded [Yes/No] | System earth ** | Short circuit level min [kA] | Short circuit level max [kA] | Distribution protection fuse [A] | Distribution protection earth fault [mA] | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Main | 400V 3P+N+E | 60 | 63 | No | S | 63 | 30 | Stahl-Syberg 8579/31-506-S001 | 8579/12-506 | RC520 RC520 RQ510 RQ220 RC140 RC140 RC550 | ||
Main | 690V 3P+E | 60 | 63 | No | R | 63 | 100 | Stahl-Syberg 8579/31-405-S001 | 8579/12-405 | RC140 RC520 RC520 RC550 RQ220 RC140 RC140 RC520 RC550 RQ510 | ||
Main | 230V 1P+N+E | 60 | 16 | Yes | S | 16 | 30 | Stahl-Syberg 8570/11-306 | 8570/12-306 | RC520 RC520 RC520 RC520 RC520 RQ220 RQ220 RQ510 RQ510 RC140 RC140 RC140 RC140 RC140 RC550 RC550 RC550 | ||
Main | 400V 3P+N+E | 60 | 125 | No | S | 125 | Stahl-Syberg 8581/31-506-S010 | 8581/12-506 | RC520 RC520 RC520 RC140 RQ220 RC550 RC550 RC140 RC140 RQ510 |
*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power
**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
Fire | NO-kontakt (kontakt=alarm) Note 1 :Må ha motstand i parallell og serie. Se typisk krets nedenfor | GHG 511 4906 R0001 6h Pin 1, 2, 3 | GHG 591 2201 R0002 6h Pin 1, 2 | RC140 RC320 RC520 RC560 RQ220 RQ320 |
ESD Battery System | Note 2: NAS / ESD 24 V signal fra SAS med linjemonitorering | 8150/1-0236-0176-150-3311 Note3: Må bruke kabel gland. Termineres i JBE på rekkeklemmer. Se type krets under | Note4: Sikkerhets rele 24V som tåler linjemonitorering. Se type krets under | |
Loss Of Pressure | NO-kontakt (kontakt=alarm) Note 1 :Må ha motstand i parallell og serie. Se typisk krets nedenfor | GHG 511 4906 R0001 6h Pin 7,8,9 | GHG 591 2201 R0002 6h Pin 7,8 | RC140 RC320 RC520 RC560 RQ220 RQ320 |
Gas | NO-kontakt (kontakt=alarm) Note 1 :Må ha motstand i parallell og serie. Se typisk krets nedenfor | GHG 511 4906 R0001 6h Pin 4, 5, 6 | GHG 591 2201 R0002, 6h Pin 4, 5 | RC140 RC320 RC520 RC560 RQ220 RQ320 |
Other | NO-kontakt (kontakt=alarm) Note 1 :Må ha motstand i parallell og serie. Se typisk krets nedenfor | GHG 511 4906 R0001 6h Pin 10, 11, 12 | GHG 591 2201 R0002 6h Pin 10, 11 | RC140 RC320 RC520 RC560 RQ220 RQ320 |
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
Telephone | Socket: STAHL 8575/11-410 10h (green) Compatible type for above STAHL 8570/11-410 12A 4P 120V 300Hz 10h (green) | Plug: STAHL 8575/12-410 10h (green) Compatible type for above STAHL 8570/12-410-S 12A 4P 120V 300Hz 10h ( green) | RC140,RC320,RC520,RC550,RC560,RQ220,RQ320 | |
Data (Fibre) | Panel contact container and Utility station end: 4-channel panel contact PBJR-LC Single Modus, 9/125 Prod.nr: 4-2x699255-7-005 Prod.name: 4-kanal PBJR kontakt-LC, AXAI, 9/125 5 meter in container end , LC plug is JS standard for patch panels Foss AS, Drammen | Drum 4-fiber field cabel, PBJR-PBJR, 9/125 Prod.nr: 3-904MIL9-3-050 Prod.name: 4-fiber PBJR plugg-PBJR plugg, 9/125 50m coiled on drum, plug both ends Foss AS, Drammen | RC140,RC320,RC520,RC550,RC560,RQ220,RQ320 | |
PA | Socket: STAHL 8575/11-404 4h (yellow) Compatible type for above STAHL 8570/11-404 16A 4P 130V 50/60Hz 4h (yellow) | Plug: STAHL 8575/12-404 4h (yellow) Compatible type for above STAHL 8570/12-404 16A 4P 130V 50/60Hz 4h (yellow) | RC140,RC320,RC520,RC550,RC560,RQ220,RQ320 |
Function | Pressure [bar] | Amount/Flow [max capacity] | Connection - type | Connection - diameter | Connection - material | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|
Sprinkler | ||||||
Drain | ||||||
Other | ||||||
Plant Air | ||||||
Instrument Air | ||||||
Seawater | ||||||
Freshwater |
Crane | 1 meter * | 2 meter * | 3 meter * |
---|---|---|---|
1 fall | 20T @ 53 meter | 20T @ 53 meter | 20T @ 53 meter |
2 fall | 40T @ 45 meter | 35,4T @ 45 meter | 31T @ 45 meter |
3 fall | 60T @ 35 meter | 50T @ 35 meter | N/A |
* Significant waveheight [max. load / max. radius]
Brann og gasssentral i konteiner | Når konteiner ikke er i bruk må «dummy plugg» støpselet settes i for å unngå feil alarmer til SKR (Henger normalt på stasjonen) Note: Motstanden mellom 13 og 14 er ikke nødvendig på JSF da ESD tripp går på egen kabel ved behov. |