Interface hook-up data sheet for Norne

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main400
3p+e
5063NoS63Socket:
STAHL
8579\1- 406 6h
Plug:
STAHL
8579\12- 406 6h
Welding socket outlets in monohull and mechanical workshop
Main230
2p+e
5016YesS1630Socket:
STAHL
8575\11- 306 6h
Plug:
STAHL
8575\12- 306 6h
Small power outlets in topside areas
Main690
3p
5012512530Socket:
STAHL
7581\11- 6h
Plug:
STAHL
7581/12- 6h
Main400
3p+N+e
5063YesS63Socket:
STAHL
8579\11- 506 6h
Plug:
STAHL
8579\12- 506 6h
Welding socket outlets at topside areas
Main230
2p+e
5016YesS1630Socket:
ABB
AUBE 216-6, 6h
Plug:
Philip Hauge
CPG216-6, 6h
Small power outlets in monohull and mechanical workshop
Main400
3p+e
5016NoS1630Socket
ABB
AUBE 316-6, 6h
Plug:
ABB
CPG 316-6, 6h
Outlets in mech. workshop
Main400
3p+e
5032NoS3230Socket
ABB
AUBE 332-6, 6h
Plug:
ABB
APG 332-6, 32 A, 6h
Outlets in mech. workshop

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
FireFire
NC *)
(åpen = alarm)
Socket:
GHG 511 4906 R0001 10A-6H Pin 1,2,3
Plug:
GHG 591 2201 R0002 10A-6H Pin 1, 2, 3.
DK. 8 - fwd container deck - L20
DK. 7 - fwd container deck - I11
P25B
ESD Battery System
Loss Of PressureNC *)
(åpen = alarm)
Socket :
GHG 511 4906 R0001 10A-6H Pin 7,8 ,9.
Plug :
GHG 591 2201 R0002 10A-6H Pin 7, 8, 9.
DK. 8 - fwd container deck - L20
DK. 7 - fwd container deck - I11
P25B
GasGas
NC *)
(åpen = alarm)
Socket:
GHG 511 4906 R0001 10A-6H Pin 4,5,6
Plug:
GHG 591 2201 R0002 10A-6H Pin 4, 5, 6.
DK. 8 - fwd container deck - L20
DK. 7 - fwd container deck - I11
P25B
OtherOther
NC *)
(åpen = alarm)
Socket
GHG 511 4906 R0001 10A-6H Pin 10,11,12
Plug:
GHG 591 2201 R0002 10A-6H Pin 10, 11, 12.
DK. 8 - fwd container deck - L20
DK. 7 - fwd container deck - I11
P25B

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
TelephoneTelephone
90 V AC ringespenning
og 48 V DC m/overlagret Audio


Socket:
GHG 531 8406 V0000 6h
Plug:
GHG 531 7406 V0000 6h
Telephone socket in JB.,
Telephone socket in JB.,
86PJE7048 in I11 area (laste/losse dk7)

JB 86PJE7047 i laste/losse område dk8
PA
100 V AC (Audiofreq)
Socket:
GHG 531 8406 V0000 6h
Plug:
GHG 531 7406 V0000 6h
PA socket in JB.,
PA socket in JB.
86AJE7162A/7163B in I11 area (laste/losse dk7)

JB 86AJE7160A/7161B dk8( laste/losse område)

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Instrument Air
Seawater
Freshwater
Drain
Plant Air
Sprinkler
Other

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
Kraner 1 - fall12,9 t./ 38,5 meter9,1 t./ 38,5 meter6,5 t./ 38,5 meter
Kraner 3 - fall35,7 t./ 16,5 meter22,6 t./ 16,5 meter14,2 t./ 16,5 meter (E)
Kraner 2 - fall27,9 t./ 23,5 meter21,6 t./ 23,5 meter16,7 t./ 23,5 meter

* Significant waveheight [max. load / max. radius]

Additional information

Eksempel på framføring av instrumentsignal i kontainer på Norne.