Power * | Volt [V] | Frequency [Hz] | Phase Current [A] | Neutral Loaded [Yes/No] | System earth ** | Short circuit level min [kA] | Short circuit level max [kA] | Distribution protection fuse [A] | Distribution protection earth fault [mA] | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Main | 230 | 50 | 16 | Yes | S | 7 | 16 | Stikk. / Socket: CEAG: GHG 543 0008 R0676 (blue) 6h 1P + N + PE | Støpsel / Plug : CEAG: GHG 543 2306 V0000 (blue) 6h 1P + N + PE | Bare for lys og mindre oppvarmingsformål / Only for lighting and minor heating purpose | ||
Main | 400 | 50 | 63 | Yes | S | 7 | 63 | Stikk. / Socket: CEAG: GHG 534 0002 R1096 (red) 6h 3P + N + PE | Støpsel / Plug : CEAG: GHG 534 2506 V0000 (red) 6h 3P + N + PE | Maks / Max 20 kW | ||
Main | 690 | 50 | 125 | No | R | 50 | 200 | Stikk. / Socket: CEAG: GHG 515 4505 R0001 (blac) 5h 3P + N + PE | Støpsel / Plug : CEAG: GHG 515 7505 R0001 (blac) 5h 3P + N + PE | Maks / Max 60 kW Mulighet for tilkopling samt metode for tilkopling må avtales i hvert enkelt tilfelle. / Possibility for connection as well as method for connection to be arranged in every particularly case. |
*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power
**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
Loss Of Pressure | Tilkopling i koplingsboks / Connection in junction box | N/A | ||
Fire | NO-kontakt *** NO-contact *** (kontakt = alarm) (contact=alarm) | Tilkopling i koplingsboks / Connection in junction box | Via kabel 2x1,5 mm2, 35 m / Via cable 2x1,5 mm2, 35 m | W21 Nord-Sør D60 / W21 North-South D60 |
Gas | NO-kontakt *** NO-contact *** (kontakt = alarm) (contact=alarm) | Tilkopling i koplingsboks / Connection in junction box | Via kabel 2x1,5 mm2, 35 m / Via cable 2x1,5 mm2, 35 m | W21 Nord-Sør D60 / W21 North-South D60 |
Other | Tilkopling i koplingsboks / Connection in junction box | Via kabel 2x1,5 mm2, 35 m / Via cable 2x1,5 mm2, 35 m | W21 Nord-Sør D60 / W21 North-South D60 | |
ESD Battery System | Tilkopling i koplingsboks / Connection in junction box | Intern forrigling i kontainer / Internal interlocking in container |
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
Telephone | Socket outlet: STAHL 8570/11-410 (green) | Plug: STAHL 8570/12-410 (green) L1, L2 | W21 Nord-Sør D60 / W21 North-South D60 | |
PA | Socket outlet: STAHL 8575/11-404 (yellow) | Plug: STAHL 8575/12-404 (yellow) L1, L2 | W21 Nord-Sør D60 / W21 North-South D60 |
Function | Pressure [bar] | Amount/Flow [max capacity] | Connection - type | Connection - diameter | Connection - material | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|
Plant Air | 8 9 | |||||
Freshwater | 7 9 | |||||
Instrument Air | 8 9 | |||||
Sprinkler | - | |||||
Seawater | 9 | |||||
Drain | - | |||||
Other | - |
Crane | 1 meter * | 2 meter * | 3 meter * |
---|---|---|---|
1-fall | 15t/48m | 14,7t/48m | 12,6t/48m |
2-fall | 33t/29,9m | 33t/29,9m | 29,6t/25m |
3-fall | 50t/22m | 50t/22m | 45t/15m |
* Significant waveheight [max. load / max. radius]
KORTSLUTNINGSNIVÅ
Verdiene vil være ved kortslutning i selve tavlen.
Kortslutningsnivået i/ved tavlen i det midlertidige utstyret vil være lavere.
Ved beregning av kortslutningsnivå kan følgende parametre brukes:
* Fra installasjonens hovedtavle og via fast opplagt kabel til stikkontakt/tilkoplingspunkt for midlertidig utstyr 3x25mm2 - 50 m.
* Fra installasjonens stikkontakt/tilkoplingspunkt for det midlertidige utstyret og via bevegelig kabel til utstyret 3 x 16mm2 -35 m.
SHORT CIRCUIT LEVEL
Values reflect short circuit level inside the switchboard
Regarding switchboard for temporary equipment the short circuit level inside or at the switchboard will be lower
When calculating the level of the short circuit following parameters can be used:
* From the facilitys main switchboard and via fixed cabling to the socked/connection point for temporary equipment; 3x25mm2 - 50 m.
* From the facilitys socked/connection point for temporary equipment and via flexible cables to the equipment; 3 x 16mm2 - 35 m.