Interface hook-up data sheet for Oseberg Sør

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main2305016YesS716Stikk. / Socket:
CEAG: GHG 543
0008 R0676
(blue) 6h
1P + N + PE
Støpsel / Plug :
CEAG: GHG 543
2306 V0000
(blue) 6h
1P + N + PE
Bare for lys og mindre oppvarmingsformål /
Only for lighting and minor heating purpose
Main4005063YesS763Stikk. / Socket:
CEAG: GHG 534
0002 R1096
(red) 6h
3P + N + PE
Støpsel / Plug :
CEAG: GHG 534
2506 V0000
(red) 6h
3P + N + PE
Maks / Max 20 kW
Main69050125NoR50200Stikk. / Socket:
CEAG: GHG 515
4505 R0001
(blac) 5h
3P + N + PE
Støpsel / Plug :
CEAG: GHG 515
7505 R0001
(blac) 5h
3P + N + PE
Maks / Max 60 kW

Mulighet for tilkopling samt metode for tilkopling må avtales i hvert enkelt tilfelle. /
Possibility for connection as well as method for connection to be arranged in every particularly case.

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Loss Of PressureTilkopling i koplingsboks /
Connection in junction box
N/A
FireNO-kontakt ***
NO-contact ***
(kontakt = alarm)
(contact=alarm)
Tilkopling i koplingsboks /
Connection in junction box
Via kabel 2x1,5 mm2, 35 m /
Via cable 2x1,5 mm2, 35 m
W21 Nord-Sør D60 /
W21 North-South D60
GasNO-kontakt ***
NO-contact ***
(kontakt = alarm)
(contact=alarm)
Tilkopling i koplingsboks /
Connection in junction box
Via kabel 2x1,5 mm2, 35 m /
Via cable 2x1,5 mm2, 35 m
W21 Nord-Sør D60 /
W21 North-South D60
OtherTilkopling i koplingsboks /
Connection in junction box
Via kabel 2x1,5 mm2, 35 m /
Via cable 2x1,5 mm2, 35 m
W21 Nord-Sør D60 /
W21 North-South D60
ESD Battery SystemTilkopling i koplingsboks /
Connection in junction box
Intern forrigling i kontainer /
Internal interlocking in container

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
TelephoneSocket outlet:
STAHL 8570/11-410
(green)
Plug:
STAHL 8570/12-410
(green) L1, L2
W21 Nord-Sør D60 /
W21 North-South D60
PASocket outlet:
STAHL 8575/11-404
(yellow)
Plug:
STAHL 8575/12-404
(yellow) L1, L2
W21 Nord-Sør D60 /
W21 North-South D60

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Plant Air8 – 9
Freshwater7 – 9
Instrument Air8 – 9
Sprinkler-
Seawater9
Drain-
Other-

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
1-fall15t/48m14,7t/48m12,6t/48m
2-fall33t/29,9m33t/29,9m29,6t/25m
3-fall50t/22m50t/22m45t/15m

* Significant waveheight [max. load / max. radius]

Comments

KORTSLUTNINGSNIVÅ
Verdiene vil være ved kortslutning i selve tavlen.
Kortslutningsnivået i/ved tavlen i det midlertidige utstyret vil være lavere.

Ved beregning av kortslutningsnivå kan følgende parametre brukes:
* Fra installasjonens hovedtavle og via fast opplagt kabel til stikkontakt/tilkoplingspunkt for midlertidig utstyr 3x25mm2 - 50 m.
* Fra installasjonens stikkontakt/tilkoplingspunkt for det midlertidige utstyret og via bevegelig kabel til utstyret 3 x 16mm2 -35 m.

SHORT CIRCUIT LEVEL
Values reflect short circuit level inside the switchboard
Regarding switchboard for temporary equipment the short circuit level inside or at the switchboard will be lower

When calculating the level of the short circuit following parameters can be used:
* From the facility’s main switchboard and via fixed cabling to the socked/connection point for temporary equipment; 3x25mm2 - 50 m.
* From the facility’s socked/connection point for temporary equipment and via flexible cables to the equipment; 3 x 16mm2 - 35 m.