Interface hook-up data sheet for Oseberg Øst

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main2305016YesS1016Stikk. / Socket:
ABB: GHG 543
1306 V0
(blue) 6h
2P + PE
Støpsel / Plug :
ABB: GHG 543 2306 V0
(blue) 6h
2P + PE
Bare for lys og mindre oppvarmingsformål /
Only for lighting and minor heating purpose
Main69050125NoS10125Stikk. / Socket:
CEAG: GHG 515 4405 R3001
3P+PE
(black) 5h
Støpsel / Plug :
CEAG: GHG515 7405
R0001
3P+PE
(black) 5h
C41, C43 og M12

Note : Interface to 690 V box at M12
Main4005063YesS1063Stikk. / Socket:
ABB: GHG 534
1506 V0
(red) 6h
3P + N + PE
Støpsel / Plug :
ABB: GHG 534 2506 V0000
(red) 6h
3P + N + PE
Maks / Max 43.6 kW

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
OtherTilkopling i koplingsboks /
Connection in junction box



For C32 benyttes Socket outlet CEAG GHG 511V4906 R3001 Common Alarm
Plug:
CEAG
GHG 591 2201 R0002
Common Alarm pin 10, 11
C41, M12 og C32 : Se kommentarer under tabell.
Vedrørende koblingsboks på M12 benyttes koblingsboks, med tilrettelagt for potensialfrie åpne kontakter. Termineres likt som for stikk.


C41, M12 og C32: See comments below table.
Regarding connection at M12 interface is in a junction box, with potential free normally open contacts. Termination equal to plug connection.
Loss Of PressureTilkopling i koplingsboks /
Connection in junction box

For C32 benyttes Socket outlet CEAG GHG 511V4906 R3001
Plug:
CEAG GHG 591 2201 R0002
pin 7, 8
C41, M12 og C32 : Se kommentarer under tabell.
Vedrørende koblingsboks på M12 benyttes koblingsboks. Gjelder all norsk teekst nedover i kolonnen.

C41, M12 og C32: See comments below table.
Regarding connection at M12 interface is in a junction box, with potential free normally open contacts. Termination equal to plug connection.
FireStikk. / Socket:
HAWKE M25
EEx d IIC T6
TamB -30 +60 degree
Cert.no.Ex96D 1062x

For C32 benyttes Socket outlet CEAG GHG 511V4906 R3001
Plug:
CEAG
GHG 591 2201 R0002
pin 1, 2

CEAG GHG 511 4906 R3001
C41, M12 og C32 : Se kommentarer under tabell.
Vedrørende koblingsboks på M12 benyttes koblingsboks, med tilrettelagt for potensialfrie åpne kontakter. Termineres likt som for stikk.

C41, M12 og C32: See comments below table.
Regarding connection at M12 interface is in a junction box, with potential free normally open contacts. Termination equal to plug connection.
GasTilkopling i koplingsboks /
Connection in junction box



For C32 benyttes Socket outlet CEAG GHG 511V4906 R3001
Plug:
CEAG
GHG 591 2201 R0002
pin 4, 5
C41, M12 og C32 : Se kommentarer under tabell.
Vedrørende koblingsboks på M12 benyttes koblingsboks, med tilrettelagt for potensialfrie åpne kontakter. Termineres likt som for stikk.


C41, M12 og C32: See comments below table.
Regarding connection at M12 interface is in a junction box, with potential free normally open contacts. Terminationequal to plug connection.
ESD Battery SystemTilkopling i koplingsboks /
Connection in junction box
C41 : Se kommentarer under tabell

C41: See comments below table

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
PAStikk. / Socket: HAWKE M25 EEx d IIC T6
TamB -30 +60 degree Cert.no.Ex96D 1062x

Socket outlet:
Stahl-Syberg
8575/11-404 4P Gul
Plug: Stahl-Syberg
8570/11-404 4 Gul.

Plug:
Stahl-Syberg
8575/12-404 4P Gul
C41 og C32 : Se kommentarer under tabell
C41: See comments below table


For C11 and C32 area
TelephoneStikk. / Socket: HAWKE M25 EEx d IIC T6
TamB -30 +60 degree Cert.no.Ex96D 1062x

Socket outlet:
Stahl-Syberg
8575/11-402 4P Grønn
Plug: Stahl-Syberg
8570/11-402 Grønn

Plug:Stahl-Syberg
8575/12-402 4P Grønn
C41 og C32 : Se kommentarer under tabell
C41: See comments below table


For C11 and C32 area
Data (Fibre)Multimode fiber ST-connector inside junction box (OP-IS) .
C32

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Instrument Air 8,0
Seawater
Drain
Other
Plant Air 8,0
Sprinkler
Freshwater 8,0

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
2-fall33t/29,9m33t/29,9m29,6t/25m
3-fall50t/22m50t/22m45t/15m
1-fall15t/48m14,7t/48m12,6t/48m

* Significant waveheight [max. load / max. radius]

Comments

INSTRUMENT
Vedrørende tilkopling på stasjon C41og C32 benyttes plugg: CEAG GHG 591 2201 (21 pins plugg) med potensialfrie normalt åpne kontakter.
* Tap av trykk: pin 7 og 8
* Brann: pin 1 og 2
* Gass: pin 4 og 5
* Fellesalarm: 10 og 11

Regarding connection at station C41 and C32 following plug shall apply; CEAG GHG 591 2201 (21 pins plug) with potential free normal open contacts
* Loss of pressure: pin 7 & 8
* Fire: pin 1 & 2
* Gas: pin 4 & 5
* Common alarm: pin 10 & 11

KORTSLUTNINGSNIVÅ
Verdiene vil være ved kortslutning i selve tavlen.
Kortslutningsnivået i/ved tavlen i det midlertidige utstyret vil være lavere.

Ved beregning av kortslutningsnivå kan følgende parametre brukes:
* Fra installasjonens hovedtavle og via fast opplagt kabel til stikkontakt/tilkoplingspunkt for midlertidig utstyr 3x25mm2 - 50 m.
* Fra installasjonens stikkontakt/tilkoplingspunkt for det midlertidige utstyret og via bevegelig kabel til utstyret 3 x 16mm2 -35 m.

SHORT CIRCUIT LEVEL
Values reflect short circuit level inside the switchboard
Regarding switchboard for temporary equipment the short circuit level inside or at the switchboard will be lower

When calculating the level of the short circuit following parameters can be used:
* From the facility’s main switchboard and via fixed cabling to the socked/connection point for temporary equipment; 3x25mm2 - 50 m.
* From the facility’s socked/connection point for temporary equipment and via flexible cables to the equipment; 3 x 16mm2 - 35 m.