Power * | Volt [V] | Frequency [Hz] | Phase Current [A] | Neutral Loaded [Yes/No] | System earth ** | Short circuit level min [kA] | Short circuit level max [kA] | Distribution protection fuse [A] | Distribution protection earth fault [mA] | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Main | 230 | 50 | 16 | Yes | S | 10 | 16 | Stikk. / Socket: ABB: GHG 543 1306 V0 (blue) 6h 2P + PE | Støpsel / Plug : ABB: GHG 543 2306 V0 (blue) 6h 2P + PE | Bare for lys og mindre oppvarmingsformål / Only for lighting and minor heating purpose | ||
Main | 690 | 50 | 125 | No | S | 10 | 125 | Stikk. / Socket: CEAG: GHG 515 4405 R3001 3P+PE (black) 5h | Støpsel / Plug : CEAG: GHG515 7405 R0001 3P+PE (black) 5h | C41, C43 og M12 Note : Interface to 690 V box at M12 | ||
Main | 400 | 50 | 63 | Yes | S | 10 | 63 | Stikk. / Socket: ABB: GHG 534 1506 V0 (red) 6h 3P + N + PE | Støpsel / Plug : ABB: GHG 534 2506 V0000 (red) 6h 3P + N + PE | Maks / Max 43.6 kW |
*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power
**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
Other | Tilkopling i koplingsboks / Connection in junction box For C32 benyttes Socket outlet CEAG GHG 511V4906 R3001 Common Alarm | Plug: CEAG GHG 591 2201 R0002 Common Alarm pin 10, 11 | C41, M12 og C32 : Se kommentarer under tabell. Vedrørende koblingsboks på M12 benyttes koblingsboks, med tilrettelagt for potensialfrie åpne kontakter. Termineres likt som for stikk. C41, M12 og C32: See comments below table. Regarding connection at M12 interface is in a junction box, with potential free normally open contacts. Termination equal to plug connection. | |
Loss Of Pressure | Tilkopling i koplingsboks / Connection in junction box For C32 benyttes Socket outlet CEAG GHG 511V4906 R3001 | Plug: CEAG GHG 591 2201 R0002 pin 7, 8 | C41, M12 og C32 : Se kommentarer under tabell. Vedrørende koblingsboks på M12 benyttes koblingsboks. Gjelder all norsk teekst nedover i kolonnen. C41, M12 og C32: See comments below table. Regarding connection at M12 interface is in a junction box, with potential free normally open contacts. Termination equal to plug connection. | |
Fire | Stikk. / Socket: HAWKE M25 EEx d IIC T6 TamB -30 +60 degree Cert.no.Ex96D 1062x For C32 benyttes Socket outlet CEAG GHG 511V4906 R3001 | Plug: CEAG GHG 591 2201 R0002 pin 1, 2 CEAG GHG 511 4906 R3001 | C41, M12 og C32 : Se kommentarer under tabell. Vedrørende koblingsboks på M12 benyttes koblingsboks, med tilrettelagt for potensialfrie åpne kontakter. Termineres likt som for stikk. C41, M12 og C32: See comments below table. Regarding connection at M12 interface is in a junction box, with potential free normally open contacts. Termination equal to plug connection. | |
Gas | Tilkopling i koplingsboks / Connection in junction box For C32 benyttes Socket outlet CEAG GHG 511V4906 R3001 | Plug: CEAG GHG 591 2201 R0002 pin 4, 5 | C41, M12 og C32 : Se kommentarer under tabell. Vedrørende koblingsboks på M12 benyttes koblingsboks, med tilrettelagt for potensialfrie åpne kontakter. Termineres likt som for stikk. C41, M12 og C32: See comments below table. Regarding connection at M12 interface is in a junction box, with potential free normally open contacts. Terminationequal to plug connection. | |
ESD Battery System | Tilkopling i koplingsboks / Connection in junction box | C41 : Se kommentarer under tabell C41: See comments below table |
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
PA | Stikk. / Socket: HAWKE M25 EEx d IIC T6 TamB -30 +60 degree Cert.no.Ex96D 1062x Socket outlet: Stahl-Syberg 8575/11-404 4P Gul | Plug: Stahl-Syberg 8570/11-404 4 Gul. Plug: Stahl-Syberg 8575/12-404 4P Gul | C41 og C32 : Se kommentarer under tabell C41: See comments below table For C11 and C32 area | |
Telephone | Stikk. / Socket: HAWKE M25 EEx d IIC T6 TamB -30 +60 degree Cert.no.Ex96D 1062x Socket outlet: Stahl-Syberg 8575/11-402 4P Grønn | Plug: Stahl-Syberg 8570/11-402 Grønn Plug:Stahl-Syberg 8575/12-402 4P Grønn | C41 og C32 : Se kommentarer under tabell C41: See comments below table For C11 and C32 area | |
Data (Fibre) | Multimode fiber | ST-connector inside junction box (OP-IS) . | C32 |
Function | Pressure [bar] | Amount/Flow [max capacity] | Connection - type | Connection - diameter | Connection - material | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|
Instrument Air | 8,0 | |||||
Seawater | ||||||
Drain | ||||||
Other | ||||||
Plant Air | 8,0 | |||||
Sprinkler | ||||||
Freshwater | 8,0 |
Crane | 1 meter * | 2 meter * | 3 meter * |
---|---|---|---|
2-fall | 33t/29,9m | 33t/29,9m | 29,6t/25m |
3-fall | 50t/22m | 50t/22m | 45t/15m |
1-fall | 15t/48m | 14,7t/48m | 12,6t/48m |
* Significant waveheight [max. load / max. radius]
INSTRUMENT
Vedrørende tilkopling på stasjon C41og C32 benyttes plugg: CEAG GHG 591 2201 (21 pins plugg) med potensialfrie normalt åpne kontakter.
* Tap av trykk: pin 7 og 8
* Brann: pin 1 og 2
* Gass: pin 4 og 5
* Fellesalarm: 10 og 11
Regarding connection at station C41 and C32 following plug shall apply; CEAG GHG 591 2201 (21 pins plug) with potential free normal open contacts
* Loss of pressure: pin 7 & 8
* Fire: pin 1 & 2
* Gas: pin 4 & 5
* Common alarm: pin 10 & 11
KORTSLUTNINGSNIVÅ
Verdiene vil være ved kortslutning i selve tavlen.
Kortslutningsnivået i/ved tavlen i det midlertidige utstyret vil være lavere.
Ved beregning av kortslutningsnivå kan følgende parametre brukes:
* Fra installasjonens hovedtavle og via fast opplagt kabel til stikkontakt/tilkoplingspunkt for midlertidig utstyr 3x25mm2 - 50 m.
* Fra installasjonens stikkontakt/tilkoplingspunkt for det midlertidige utstyret og via bevegelig kabel til utstyret 3 x 16mm2 -35 m.
SHORT CIRCUIT LEVEL
Values reflect short circuit level inside the switchboard
Regarding switchboard for temporary equipment the short circuit level inside or at the switchboard will be lower
When calculating the level of the short circuit following parameters can be used:
* From the facilitys main switchboard and via fixed cabling to the socked/connection point for temporary equipment; 3x25mm2 - 50 m.
* From the facilitys socked/connection point for temporary equipment and via flexible cables to the equipment; 3 x 16mm2 - 35 m.