Interface hook-up data sheet for Sleipner A

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main440
3p+e
6063NoS63Socket:
GHG 534 1407 V0 7h
Plug:
GHG 534 2407 V0 7h
C06-D21T-M22W(east-west-senter), D21D,M23M,
M24W (east-west), M25T.
+sockets all over the platform
UPS230
2p+e
6016NoI16Socket:
GHG 543 4306 V0 6h
Plug:
GHG 543 2306 V0 6h
C14-C13 - C03-C12
For Artemis
Main230
2p+e
6016NoS16Socket:
GHG 543 4306 V0 6h
Plug:
GHG 543 2306 V0 6h
C06-D21T-M22W(east-west-senter), D21D,M23M,
M24W (east-west), M25T.
+sockets all over the platform
Main44060200NoS200Junction box M25 lower mezz
Main44060400NoS3003000Weidemuller rack U00- C04D- C05D- M22D- M22LM- M22M
Main440
3p+N+e
60125NoSSocket:
GHG 536 4507 V0 7h
Plug:
GHG 535 2507 V0 7h
M22W og D22M For Wireline winch

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
OtherNO-kontakt
(kontakt=alarm)
Socket:
GHG 591 1201 R2 6h Pin 10, 11, 12
Plug:
GHG 591 2201 R2 6h Pin 10, 11, 12
C06- D21T- M22W (east-west-senter)- M22D - M24W2 stk (east-west) - M25T-D21D-M23M.
ESD Battery System
Loss Of PressureNO-kontakt
(kontakt=alarm)
Socket:
GHG 591 1201 R2 6h Pin 7, 8, 9
Plug:
GHG 591 2201 R2, 6h Pin 7, 8, 9,
C06- D21T- M22W (east-west-senter)- M22D - M24W2 stk (east-west) - M25T-D21D-M23M.
FireNO-kontakt
(kontakt=alarm)
Socket:
GHG 591 1201 R2 6h Pin 1, 2, 3
Plug:
GHG 591 2201 R2 6h Pin 1, 2, 3
C06- D21T- M22W (east-west-senter)- M22D - M24W2 stk (east-west) - M25T-D21D-M23M.
GasNO-kontakt
(kontakt=alarm)
Socket:
GHG 591 1201 R2 6h Pin 4, 5, 6
Plug:
GHG 591 2201 R2, 6h Pin 4, 5, 6,
C06- D21T- M22W (east-west-senter)- M22D - M24W2 stk (east-west) - M25T-D21D-M23M.

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
PASocket:
STAHL 8575/11-404 4h (yellow)
Plug:
STAHL 8575/12-404 4h (yellow)
C06- D21T- M22W (east-west-senter)- M22D - M24W2 stk (east-west) - M25T-D21D-M23M.
TelephoneSocket:
STAHL 8575/11-410 10h (green)
Plug:
STAHL 8575/12-410 10h (green)
C06- D21T- M22W (east-west-senter)- M22D - M24W2 stk (east-west) - M25T-D21D-M23M.
CCTVSocket:
STAHL 8575/11-506 6h (red)
Plug:
STAHL 8575/12-506 6h (red)
D22, D31

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Instrument Air
Sprinkler
Freshwater
Plant Air
Seawater
Drain
Other

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
Kraner 44 t./ 25 meter34,7 t./ 25 meter26,6 t./ 25 meter

* Significant waveheight [max. load / max. radius]

Comments

I TABELLEN VISES MAKS. LØFTEKAPASITET FOR LØFT MED STORBLOKK FRA FORSYNINGSSKIP (tonn) I FORHOLD TIL SIGNIFIKANT BØLGEHØYDE (meter).

Additional information

Eksempel på framføring av instrumentsignal i kontainer på Sleipner. Alternative løsninger aksepteres, men signalkontakter og motstander skal være tilkoplet pinnene i støpselet slik som vist.