Interface hook-up data sheet for Snorre A

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main660
3p+N+E
6063NoR30
Note 1
63Plug:
ABB GHG 534-2505 V0
Max load 36 kW
Main230
2p+e
6016NoS1016Only for lighting and small heating purposes etc.Plug:
ABB GHG 543-2306 V0
Main4406063NoS1063Plug:
GHG 5147407R 0001
(CEAG 500 V 63A EEx)
Socket outlets: 2 off in module D07 and 1 off in each of the following modules: P11, P51, P55 and W15
Main660
3p+N+E
60125NoR30
Note 1
125Plug:
ABB GHG 535-2505 V0
Max load 60 kW

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
FireN/O
Resistor in parallel 3.3 kohm
QK0189S
Rota 18 way IS Quickon plug -
CP077 2520
(Supplied by installation)
Pin: 3-4
QK0203S
Rota 18 way socket IS QK0203S - CS0076
3050
(Supplied by vendor)
Pin: 3-4
D37, Pipedekk
W25, Lukedekk S
W45, Lukedekk N
Loss Of PressureN/O
Resistor in parallel 3.3 kohm
QK0189S
Rota 18 way IS Quickon plug -
CP077 2520
(Supplied by installation)
Pin: 9-10
QK0203S
Rota 18 way socket IS QK0203S - CS0076
3050
(Supplied by vendor)
Pin: 9-10
D37, Pipedekk
W25, Lukedekk S
W45, Lukedekk N
GasN/O
Resistor in parallel 3.3 kohm
QK0189S
Rota 18 way IS Quickon plug -
CP077 2520
(Supplied by installation)
Pin: 1-2
QK0203S
Rota 18 way socket IS QK0203S - CS0076
3050
(Supplied by vendor)
Pin: 1-2
D37, Pipedekk
W25, Lukedekk S
W45, Lukedekk N
OtherManual Alarm:
N/O
Resistor in parallel 3.3 kohm



Healthy:
N/O
Resistor in parallel 3.3 kohm



Connected:
N/O
3.3kohm resistor to be installed for signal for "Connected" between T-U

Please read also Note 2 in section "General Comments" below.
QK0189S
Rota 18 way IS Quickon plug -
CP077 2520
(Supplied by installation)
Pin: 7-8

Healthy:
QK0189S
Rota 18 way IS Quickon plug -
CP077 2520
(Supplied by installation)
Pin: 5-6

Connected:
QK0189S
Rota 18 way IS Quickon plug -
CP077 2520
(Supplied by installation)
Pin: 17-18
QK0203S
Rota 18 way socket IS QK0203S - CS0076
3050
(Supplied by vendor)
Pin: 7-8

Healthy:
QK0203S
Rota 18 way socket IS QK0203S - CS0076
3050
(Supplied by vendor)
Pin: 5-6

Connected:
QK0203S
Rota 18 way socket IS QK0203S - CS0076
3050
(Supplied by vendor)
Pin: 17-18
Manual Alarm:
D37, Pipedekk
W25, Lukedekk S
W45, Lukedekk N



Healthy:
D37, Pipedekk
W25, Lukedekk S
W45, Lukedekk N



Connected:
D37, Pipedekk
W25, Lukedekk S
W45, Lukedekk N
ESD Battery System

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
PAPlug:
STAHL, type: 8575/12-404 (Gul)
Område:
D07,D55,P25,P55,W15,W55
TelephonePlug:
STAHL, type: 8575/12-402 (Grønn)
Område:
D07,D55,P25,P55,W15,W55
Other (insert)
Data (Fibre)Multimode fiberSocket: 4-fiber PBJR 62,5/125 Plugg: 4-fiber PBJR Plug - SC 62,5/125 D07,D55,W15,W55

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Plant Air8,5
Instrument Air8,5
Sprinkler8,5
Freshwater7,8
Drain-
Other
Seawater8,5

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
Nordkran60t./ 22 meter 53,2 t./ 20 meter 29,4 t./ 27,5 meter
Sørkran60 t./ 22 meter53,2 t./ 20 meter29,4 t./ 27,5 meter

* Significant waveheight [max. load / max. radius]

Comments

I TABELLEN VISES MAKS. LØFTEKAPASITET FOR LØFT MED STORBLOKK FRA FORSYNINGSSKIP (tonn) I FORHOLD TIL SIGNIFIKANT BØLGEHØYDE (meter).

Additional information

Note 1
The short circuit (SC) levels stated are for SC in the feeding switchboard on the platform itself. The SC level in/near the temporary equipment's own switchboard is lower.
For calculation of SC levels the following parameters may be used:
From platforms main switchboard and via fixed cable to socket outlet / junction box for temporary equipment: 3 x 25 mm2 - 50 m.
From platforms socket outlet / junction box for temporary equipment and via flexible cable for temporary equipment: 3 x 16 mm2 - 35 m.
440 V 3-phase is in limited amount available from portabable transformers. Need for 440 V to be identified / evaluated in each case.

Note 2
For instrument interface between temporary equipment and platform, please confer attached scetch "Snorre A Container Instrument Hook-up"