Power * | Volt [V] | Frequency [Hz] | Phase Current [A] | Neutral Loaded [Yes/No] | System earth ** | Short circuit level min [kA] | Short circuit level max [kA] | Distribution protection fuse [A] | Distribution protection earth fault [mA] | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Main | 440 | 60 | 300 | No | S | 300 | Termination in Junction box | Two JB W17 West and W16 Wvest | ||||
Main | 440 3p+e | 60 | 63 | No | S | 63 | Socket: GHG 534 1407 V0 7h | Plug: GHG 534 2407 V0 7h | Two sockets W16 West og W17 West. | |||
Main | 230 2p+e | 60 | 16 | No | S | 16 | Socket: STAHL 8575/13-306 6h | Plug: STAHL 8570/12-306 6h | All over the platform | |||
Main | 440 3p+N+e | 60 | 125 | No | S | 125 | Socket: GHG 536 4507 V0 7h | Plug: GHG 535 2507 V0 7h | Two sockets W16 West and W17 West. One socket at W18. One socket at M04 north (W14) and one socket at M06 south (W14) | |||
Main | 440 3p+e | 60 | 32 | No | S | 32 | Socket: GHG 532 4407 V0 7h | Plug: GHG 532 7407 V0 7h | Six sockets in W-moduls (Drilling) |
*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power
**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
Fire | NO | Socket: GHG 591 1201 R2 Pin 1, 2, 3 | Plug: GHG 591 2201 R2 Pin 1, 2, 3 | W16T/W17T/M04T/ M06T |
Gas | NO | Socket: GHG 591 1201 R2 Pin 4, 5, 6 | Plug: GHG 591 2201 R2 Pin 4, 5, 6 | W16T/W17T/M04T/ M06T |
Other | NC (Common Fault) NO (FAA) | Socket: GHG 591 1201 R2 Pin 10, 11, 12 Pin 13, 14, 15 | Plug: GHG 591 2201 R2 Pin 10, 11, 12 Pin 13, 14, 15 | W16T/W17T/M04T/ M06T |
ESD Battery System | ||||
Loss Of Pressure | NO | Socket: GHG 591 1201 R2 Pin 7, 8, 9 | Plug: GHG 591 2201 R2 Pin 7, 8, 9 | W16T/W17T/M04T/ M06T |
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
PA | Socket: STAHL 8575/11-404 (Yw) | Plug: STAHL 8575/11-404-4h (Yw) | ||
Telephone | Socket: STAHL 8575/11-402 (Green) | Plug: STAHL 8575/11-402-2h (Green) |
Function | Pressure [bar] | Amount/Flow [max capacity] | Connection - type | Connection - diameter | Connection - material | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|
Sprinkler | ||||||
Freshwater | ||||||
Other | ||||||
Plant Air | ||||||
Instrument Air | ||||||
Seawater | ||||||
Drain |
Crane | 1 meter * | 2 meter * | 3 meter * |
---|---|---|---|
Kran 3 | 44 t./16 meter (38t/20m) | 34,4 t./ 20 meter (25,7 / 20 m) | |
Kran 1 | 50 t./ 22 meter | 46,7 t./ 20 meter | |
Kran 2 | 50 t./ 22 meter | 46,7 t./ 20 meter |
* Significant waveheight [max. load / max. radius]
I TABELLEN VISES MAKS. LØFTEKAPASITET FOR LØFT MED STORBLOKK FRA FORSYNINGSSKIP (tonn) I FORHOLD TIL SIGNIFIKANT BØLGEHØYDE (meter).