Interface hook-up data sheet for Troll B

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main2306063NoS1063Stikk. / Socket:
CEAG: GHG 514
4409 R1
(blue) 9h
3P + PE
Støpsel / Plug :
CEAG: GHG 514 7409 R1/
GHG 534 2409 V0
(blue) 9h
3P + PE
Laydown area
G40, C50, Z12, M24
Main2306016NoS1016Stikk. / Socket:
CEAG: GHG 511
4306 R1
(blue) 6h
2P + PE
Støpsel / Plug :
CEAG: GHG 511 7306 R1/
GHG 543 2306 V0
(blue) 6h
2P + PE
Laydown area
G40, C50, Z12, M24
Main6606063NoR6063Stikk. / Socket:
CEAG: GHG 514
4405 R1
(black) 5h
3P + PE
Støpsel / Plug :
CEAG: GHG 514 7405 R1/
GHG 534 2405 V0
(black) 5h
3P + PE
Laydown area
G40, C50, Z12, M24

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
GasNO-kontakt
Kontakt =alarm
Stikk. / Socket:
CEAG: GHG 511 4906 R1 (black)
21-pol, pin 4,5
Støpsel / Plug :
CEAG: GHG 591 2201 R2 (black)
21-pol, pin 4,5
Laydown area
G40, C50, Z12, M24
OtherNO-kontakt
Kontakt =alarm
Stikk. / Socket:
CEAG: GHG 511 4906 R1 (black)
21-pol, pin 10,11
Støpsel / Plug :
CEAG: GHG 591 2201 R2 (black)
21-pol, pin 10,11
Laydown area
G40, C50, Z12, M24
Loss Of PressureNO-kontakt
Kontakt =alarm
Stikk. / Socket:
CEAG: GHG 511 4906 R1 (black)
21-pol, pin 7,8
Støpsel / Plug :
CEAG: GHG 591 2201 R2 (black)
21-pol, pin 7,8
Laydown area
G40, C50, Z12, M24
FireNO-kontakt
Kontakt =alarm
Stikk. / Socket:
CEAG: GHG 511 4906 R1 (black)
21-pol, pin 1,2
Støpsel / Plug :
CEAG: GHG 591 2201 R2 (black)
21-pol, pin 1,2
Laydown area
G40, C50, Z12, M24
ESD Battery System

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
PA100 VStikk. / Socket:
Stahl 8575/11-404
(yellow) 4h
4-pol, pin 1,2
Støpsel / Plug :
Stahl 8575/12-404
(yellow) 4h
4-pol, pin 1,2
Laydown area
G40, C50, Z12, M24. 1 kontakt A-system + 1 kontakt B-system
Telephone100 V DC/50 V ACStikk. / Socket:
Stahl 8575/11-402
(green) 2h
4-pol, pin 1,2
Støpsel / Plug :
Stahl 8575/12-402
(green) 2h
4-pol, pin 1,2
Laydown area
G40, C50, Z12, M24
Data (Fibre)NA
CCTVNA

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Instrument Air 8,6
Sprinkler 17,0
Drain
Other
Plant Air 8,6
Seawater 10,0
Freshwater 6,2

Lifting capacity offshore cranes

No entries to show.

Comments

KORTSLUTNINGSNIVÅ
Verdiene vil være ved kortslutning i selve tavlen.
Kortslutningsnivået i/ved tavlen i det midlertidige utstyret vil være lavere.

Ved beregning av kortslutningsnivå kan følgende parametre brukes:
* Fra installasjonens hovedtavle og via fast opplagt kabel til stikkontakt/tilkoplingspunkt for midlertidig utstyr 3x25mm2 - 50 m.
* Fra installasjonens stikkontakt/tilkoplingspunkt for det midlertidige utstyret og via bevegelig kabel til utstyret 3 x 16mm2 -35 m.


SHORT CIRCUIT LEVEL
Values reflect short circuit level inside the switchboard
Regarding switchboard for temporary equipment the short circuit level inside or at the switchboard will be lower

When calculating the level of the short circuit following parameters can be used:
* From the facility’s main switchboard and via fixed cabling to the socked/connection point for temporary equipment; 3x25mm2 - 50 m.
* From the facility’s socked/connection point for temporary equipment and via flexible cables to the equipment; 3 x 16mm2 - 35 m.

Additional information

Link til dataark -->