Power * | Volt [V] | Frequency [Hz] | Phase Current [A] | Neutral Loaded [Yes/No] | System earth ** | Short circuit level min [kA] | Short circuit level max [kA] | Distribution protection fuse [A] | Distribution protection earth fault [mA] | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Main | 400 | 50 | 63 | Yes | S | 6,3 | 63 | Stikk. / Socket: Stahl: 8579/11-506 (red) 6h 3P + N + PE | Støpsel / Plug : Stahl: 8579/12-506 (red) 6h 3P + N + PE | Maks / Max 20kW For utstyr med en motor er maks In begrenset til 55A. Dette er pga lange kabelføringer og stort spenningsfall. For equipment furnish with one motor In is restricted to 55A. This is due to long cable length and much voltage drop | ||
Main | 230 | 50 | 16 | Yes | S | 6,3 | 16 | Stikk. / Socket: Stahl: 8575/11-306 (blue) 6h 2P + PE | Støpsel / Plug : Stahl: 8575/12-306 (blue) 6h 2P + PE | Bare for lys og mindre oppvarmingsformål / Only for lighting and minor heating purpose |
*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power
**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
Loss Of Pressure | Tilkopling i koplingsboks / Connection in junction box | |||
Fire | Tilkopling i koplingsboks / Connection in junction box | |||
Gas | Tilkopling i koplingsboks / Connection in junction box | |||
Other | Tilkopling i koplingsboks / Connection in junction box | |||
ESD Battery System | Tilkopling i koplingsboks / Connection in junction box |
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
PA | Tilkopling i koplingsboks / Connection in junction box | |||
Telephone | Tilkopling i koplingsboks / Connection in junction box |
Function | Pressure [bar] | Amount/Flow [max capacity] | Connection - type | Connection - diameter | Connection - material | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|
Instrument Air | 8,7 | |||||
Freshwater | 10,0 | |||||
Drain | ||||||
Other | ||||||
Plant Air | 8,7 | |||||
Sprinkler | 9,0-15,0 | |||||
Seawater | 9,0-15,0 |
No entries to show.
KORTSLUTNINGSNIVÅ
Verdiene vil være ved kortslutning i selve tavlen.
Kortslutningsnivået i/ved tavlen i det midlertidige utstyret vil være lavere.
Ved beregning av kortslutningsnivå kan følgende parametre brukes:
* Fra installasjonens hovedtavle og via fast opplagt kabel til stikkontakt/tilkoplingspunkt for midlertidig utstyr 3x25mm2 - 50 m.
* Fra installasjonens stikkontakt/tilkoplingspunkt for det midlertidige utstyret og via bevegelig kabel til utstyret 3 x 16mm2 -35 m.
SHORT CIRCUIT LEVEL
Values reflect short circuit level inside the switchboard
Regarding switchboard for temporary equipment the short circuit level inside or at the switchboard will be lower
When calculating the level of the short circuit following parameters can be used:
* From the facilitys main switchboard and via fixed cabling to the socked/connection point for temporary equipment; 3x25mm2 - 50 m.
* From the facilitys socked/connection point for temporary equipment and via flexible cables to the equipment; 3 x 16mm2 - 35 m.