Interface hook-up data sheet for Visund

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main690V50125NoS125Socket: STAHL
8581/31-405, 3P+j
125A-5h (Black)

ESD 2.3 SHUT DOWN
Local override NAS 2.3 to NAS 1.0 switch in 690V supply for:
Cont. st 2
EN-82-0003B_06LQ

Cont.st 5
EN-82-0003B_09RW



Plug: STAHL
8581/12-405, 3P+j
125A-5h (Black)

XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK
Emg230
P+N+j
5016YesS16Socket: STAHL 8575/11-306, 2P+j 16A-6h (Blue)


ESD 2.3 SHUT DOWN
Local override NAS 2.3 to NAS 1.0 switch in 230V supply
EH-84-0108_314
Plug: STAHL
8575/12 eller 8570/12-306, 2P+j
16A-6h (Blue)
XX-00-00007, D30
Dedikert for mulig oppkopling av Z-015 diesel luftkomp. ved svikt/feil på XX-63-0000A/B
Main400 V
3P+N+
5016Yes16JB: Tranberg TEF1058
Tag: EH820303.011-J01

ESD 2.3 SHUT DOWN
XX-00-00007, D30
Main230 V
P+N+j
5016YesS16Socket: STAHL 8575/11-306, 2P+j 16A-6h (Blue)

ESD 2.3 SHUT DOWN
Plug: STAHL
8575/12 eller 8570/12-306, 2P+j
16A-6h (Blue)

XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK

Kun for lys og mindre oppvarmingsformål
Main400 V
3P+N+j
5032YesS32Socket: STAHL 8571/11-506, 3P+N+j 32A-6h (Red)

ESD 2.3 SHUT DOWN
Plug: STAHL
8571/12 eller 8578/12-406, 3P+N+J
32A-6h (Red)

XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK
Main400 V
3P+N+j
5063YesS63Socket: STAHL 8579/31-506, 3P+N+j 63A-6h (Red)

ESD 2.3 SHUT DOWN
Plug: STAHL
8579/12-506, 3P+N+J
63A-6h (Red)

XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK
Main690V50315NoS315JB: TECHNOR
TNCN 575930
3P+j

ESD 2.3 SHUT DOWN
TERMINALS:
UKH 240
70-240mm2
MAX TORQUE: 30Nm

XX-00-0006, D30 PIPE DECK
Main69050125-
450
No125-
450
JB: TECHNOR
TNCN 767630
3P+j

Tag: EN820003A.15IR-J01

ESD 2.3 SHUT DOWN
XX-00-00007, D30

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Loss Of PressureNO-kontakt
(kontakt=alarm)
Socket outlet:
GHG 591 1201 R0002 6h Pin 7,8
Plug:
GHG 591 2201 R 0002 6h Pin 7,8,

XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK
FireNO-kontakt
(kontakt=alarm)
Socket outlet:
GHG 591 1201 R0002 6h Pin 1,2
Plug:
GHG 591 2201 R 0002 6h Pin 1,2

XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK
GasNO-kontakt
(kontakt=alarm)
Socket outlet:
GHG 591 1201 R0002 6h Pin 4,5






GHG 5911 4906R0001,6h Pin 4,5
Plug:
GHG 591 2201 R 0002 6h Pin 4,5






GHG 591 2201 R 0002 6h Pin 4,5

XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK

XX-00-0007, D30
(Dedikert for mulig oppkopling av Z-015 diesel luftkomp. ved svikt/feil på XX-63-0000A/B)
OtherNO-kontakt
(kontakt=alarm)
Socket outlet:
GHG 591 1201 R0002 6h Pin 10,11
Plug:
GHG 591 2201 R 0002 6h Pin 10,11

XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK
ESD Battery System24 VDCTNCN 151510-2Cable
XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
CCTVVideoHernis Connector EX 181, 096376Hernis Connector EX 181, 096376
XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK
PA100 VSocket: STAHL 8575/11-404-4h YellowPlug: STAHL 8570/12-504-4h Yellow
XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK
Telephone100 V DC / 50 V ACSocket: STAHL 8575/11-402-2h GreenPlug: STAHL 8570/12-402-2h Green
XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK
Data (Fibre)OptiskST-connector (Bajonett kobling) placed in box TCDN302015-2

* see comment for use
-------------------------------
Alternativt
PROBEAM PBJR 4ch sokkel
ST-connector (Bajonett kobling) Medieconverter
RJ45 – Fiber, f.eks. E-100TX-FX-05

* see comment for use
-------------------------------
Alternativt fiber med PBJR 4ch plugg

XX-00-0002, D30
XX-00-0003, G30
XX-00-0004, D30
XX-00-0005, D40 (dobbel)
XX-00-0006, D30 PIPE DECK

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Drain
Other
Plant Air
Instrument Air
Sprinkler
Seawater
Freshwater

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
SB og BB Kran 1 - fall15 t./ 49,1 meter15 t./ 49,1 meter13,7 t./ 47,5 meter
SB og BB Kran 2 - fall30 t./ 33 meter27,3 t./ 30 meter22 t./ 30 meter
SB og BB Kran 3 - fall38,5 t./ 22 meter28 t./ 22 meterSvart område i lastkart

* Significant waveheight [max. load / max. radius]

Comments

I TABELLEN VISES MAKS. LØFTEKAPASITET FOR LØFT MED STORBLOKK FRA FORSYNINGSSKIP (tonn) I FORHOLD TIL SIGNIFIKANT BØLGEHØYDE (meter).

Additional information


Alt midlertidig utstyr og konteinere skal sjekkes iht Norsok Z-015 på base i Florø før forsendelse til Visund.

Oppkopling:
Equinor Elektro tar i mot konteinere og midlertidig utstyr, samt etablerer egen logg pr. konteiner / utstyr i Lotus Notes.
Equinor Elektro og Automasjon skal ifm oppkopling av nye midlertidige konteinere / utstyr kvitere for oppkopling i etablert logg.
Dersom konteiner skal være oppkoplet i mer en 6 mnd, skal det etableres FV rutiner.

Test:
Forutsetning for test er at det er etablert egen logg, samt at Elektro og Automasjon har kvitert ut oppkopling.
- Funksjonstest Elektro, samt sjekk på at vedlagt dokumentasjon er tilgjengelig
- Funksjonsteste B&G iht C&E
- Funksjonsteste PA

Nedkopling:
Når konteiner / utstyr er ferdig på Visund skal all nedkopling utføres av Equinor Elektro og Automasjon, samt logg ajour holdes.
Utstyr skal ikke fjernes fra Visund før Equinor Elektro og Automasjon har utført nedkopling og tilbakestilling av funksjoner.

Datafiber:
Ref ARIS OM105.12.04.01 krav til rekvirent
Før oppkobling og bruk må behovet for nettverk flagges slik at nødvendige switcher og porter kan konfigureres av GBS-IT før utstyret kommer ombord.
Equinor kontor-PC`er kan kobles fritt til i Equinor kontornett.
3.parts utstyr må ha dedikert nettverk dersom det ikke er forhåndsgodkjent å kobles til Equinor-nettverkene.
Det er rekvirent sitt ansvar å sette igang og følge prosessen med definering av nettverket.
Fysisk oppkobling i felt og instrumentrom utføres av Equinor automasjon.



Koblingskjema på fremføring av instrumentsignal i kontainer pr 11.12.007