Interface hook-up data sheet for Åsgard A

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main400
3P+N+
E
50YesR6330Socket:
GHG 534 0002 R0126 6h
Plug:
GHG 534 2506 V0 6h
All over
Main230
1P+N+
E
50YesS1630Socket:
GHG 543 4306 V0 6h
Plug:
GHG 543 2306 V0 6h
GHG 511 7306 V0 6h R0001
All over
Main690 3P+E50NoR12530Socket:
Ceag
GHG 5154405R0001
125A 5H 690V 3P+j
Plug:
Ceag
GHG 5157405R0001
125A 5H 690V
3P+j

See NOTE
MG22, PA14, PA16, PD13 and QA23
NOTE: Use needs special approval from installation.
Main690
3P+E
50NoR6330Socket:
GHG 534 1405 V0 5h
Plug:
GHG 534 2405 V0 5h
In turbin area

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
GasNO-kontakt
(lukket = alarm)
See comments*
Socket:
GHG 591 1201 R0002 21-pol 6h pin 4, 5
GHG 511 4906 R0001 21-pol 6h pin 4,5
Plug:
GHG 591 2201 R0002 21-pol 6h pin 4, 5
Gantry deck turret,QB21

PD13
OtherNO-kontakt
(lukket = alarm)
See comments*
Socket:
GHG 591 1201 R0002 21-pol 6h pin 10, 11
GHG 511 4906 R0001 21-pol 6h pin 10,11
Plug:
GHG 591 2201 R0002 21-pol 6h pin 10, 11
Gantry deck turret, QB21

PD13
Loss Of PressureNO-kontakt
(lukket = alarm)
See comments*
Socket:
GHG 591 1201 R0002 21-pol 6h pin 7, 8
GHG 511 4906 R0001 21-pol 6h pin 7,8
Plug:
GHG 591 2201 R2 21-pol 6h pin 7, 8
Gantry deck turret, QB21

PD13
FireNO-kontakt
(lukket = alarm)
See comments*
Socket:
GHG 591 1201 R0002 21-pol 6h pin 1, 2
GHG 511 4906 R0001 21-pol 6h pin 1,2
Plug:
GHG 591 2201 R0002 21-pol 6h pin 1, 2
Gantry deck turret, QB21

PD13
ESD Battery System

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
PASocket:
STAHL 8575\11- 404 4h
(yellow)
Plug:
STAHL 8575/12-404 4h
(yellow)
Gantry deck turret
TelephoneSocket:
STAHL 8575\11-410 10h
(green)
Plug:
STAHL 8575/12-410 10h
(green)
Gantry deck turret

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Plant Air
Seawater
Freshwater
Other
Instrument Air
Sprinkler
Drain

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
Kraner 2 - fall30 t./ 21 meter24,5 t./ 21 meter18,2 t./ 21 meter
Kraner 1 - fall15 t./ 45 meter13,5 t./ 41 meter10,6 t./ 41 meter
Kraner 3 - fall40,6 t./ 14,5 meter26 t./ 12,5 meter17,4 t./ 12,5 meter

* Significant waveheight [max. load / max. radius]

Comments

I TABELLEN VISES MAKS. LØFTEKAPASITET FOR LØFT MED STORBLOKK FRA FORSYNINGSSKIP (tonn) I FORHOLD TIL SIGNIFIKANT BØLGEHØYDE (meter).

Additional information

* Kobling på utstyr:
  • Relene som er inne i brannsentralen i kontaineren må være NDE, dette fordi at når kontainer mister spenning (singel gas) så skal ikke alarmer aktiveres.
  • Eksempel på framføring av instrumentsignal i kontainer på Åsg A. Alternative løsninger aksepteres, men signalkontakter og motstander skal være tilkoplet pinnene i støpselet slik som vist .
  • NB !! Alle fire motstandene skal inn selv om signalet ikke er i bruk. Dette for å unngå alarm i kontrollrom.