Interface hook-up data sheet for Åsgard B

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
UPS230
2P+PE
5016NoI16 Socket Outlet:
Like ELKO 1090 and THORSMAN 5951 205
Gen. plugIndoor areas, mainly in LQ
Main230
2P+PE
5016YesS16 Socket Outlet:
Like ELKO 1090 and THORSMAN 5951 205
Gen. plugIndoor areas, mainly in LQ
Main230 2P+PE5016YesS16Socket Outlet: CEAG
GHG 543 0008 R0676
(EEx de IIC T6)
Plug: All areas
Main400
3P+N+PE
5016YesS16Socket Outlet:
CEWE CUE 416-6+R16
CEAG GHG 531 4506 VO (EEx de IIC T6)
L301, L306, L309, L318, L327, L417, L563, L564 and L582
Main400
3P+N+PE
5063YesS63Socket Outlet:
CEWE CUE 463-6+R63
CEAG GHG 534 0002 R0126 (EEx de IIC T6)

L317, L418
Welding sockets around the platform
Main400
3P+N+PE
5063YesS63Socket Outlet:
CEAG GHG 534 1506 V0 (EEx de IIC T6)
Plug:
CEAG GHG 534 2506 V0
Utility Stations in area A30, D10, D60, D80 and L20
Main400
3P+N+PE
50125YesS125Junction Box. Surface. CEAG GHG 745 EExe. II. T6. IP66EExe terminals inside junction boxUtility Stations in area A30, D10, D60, D80 and L20
UPS230
2P+PE
5016NoI16Socket Outlet for Data:
ELKO RS 1090 DATA
THORSMAN 5951 235
Data PlugIndoor areas, mainly in LQ
Main400
3P+N+PE
5032YesS32Socket Outlet:
CEWE CUE 432-6+R32

L305, L564
Main230
2P+PE
5016YesS16Socket Outlet:
CEAG GHG 543 4306 V0 (EEx de IIC T6)
Plug:
CEAG GHG 543 2306 V0
GHG 511 7306 V0 6h R0001
Utility Stations in area A30, D10, D60, D80 and L20

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
OtherGHG 591 1201 R2 21 polGHG 591 2201 R0002 21 polD10 / D60 / L26
Loss Of PressureGHG 591 1201 R2 21 polGHG 591 2201 R0002 21 polD10 / D60 / L26
FireGHG 591 1201 R2 21 polGHG 591 2201 R0002 21 polD10 / D60 / L26
GasGHG 591 1201 R2 21 polGHG 591 2201 R0002 21 polD10 / D60 / L26
ESD Battery System

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
PA100 v linjeSocket:
STAHL 8575\11- 404 4h (yellow)
Plug:
STAHL 8575/12-404 4h (yellow)
D10 / D60 / L26
TelephoneAnalog linjeSocket:
STAHL 8575\11-410 10h (green)
Plug:
STAHL 8575/12-410 10h (green)
D10 / D60 / L26

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Plant Air
Instrument Air
Seawater
Freshwater
Other
Sprinkler
Drain

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
Kran 143 t./20 meter34,7 t./20 meter27,5 t./20 meter
Kran 243 t./20 meter34,7 t./20 meter27,5 t./20 meter

* Significant waveheight [max. load / max. radius]

Comments

I TABELLEN VISES MAKS. LØFTEKAPASITET FOR LØFT MED STORBLOKK FRA FORSYNINGSSKIP (tonn) I FORHOLD TIL SIGNIFIKANT BØLGEHØYDE (meter).

Additional information

  • PT 06.09.04
  • Relene som er inne i brannsentralen i kontaineren må være NDE, dette fordi at når kontainer mister spenning (singel gas) så skal ikke alarmer aktiveres.
  • Eksempel på framføring av instrumentsignal i kontainer på Åsg B. Alternative løsninger aksepteres, men signalkontakter og motstander skal være tilkoplet pinnene i støpselet slik som vist NB !! Alle fire motstandene skal inn selv om signalet ikke er i bruk. Dette for å unngå alarm i kontrollrom.