Interface hook-up data sheet for Gina Krog

Norsok Standard Z-015

General information

Plant type: Fast innretning

Electrical

Power *
Volt [V]
Frequency [Hz]
Phase Current [A]
Neutral Loaded [Yes/No]
System earth **
Short circuit level min [kA]
Short circuit level max [kA]
Distribution protection fuse [A]
Distribution protection earth fault [mA]
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
Main690
3ph +PE
60125NoR125GHG 515 4405 R3001, SOCKET OUTLET,
Exde IIC T6
GHG 515 7405 R0001 Ex. Plug, Exde IIC T610 pc. W200, W300
Main690
3ph +PE
6063NoR63GHG 514 4405 R3001, SOCKET OUTLET, Exde IIC T6GHG 514 7405 R0001 Ex. Plug, Exde IIC T613 pc. E600, P250, P300, P350, P400, P600, W100, W200, W300
Main690
3ph +PE
6032NoR32GHG 512 4405 R3001, SOCKET OUTLET, Exde IIC T6GHG 512 7405 R0001 Ex. Plug, Exde IIC T67 pc. Q300, W200, W300
Main400
3ph
+N
+PE
60125YesS125GHG 515 4506 R3001, SOCKET OUTLET,
Exde IIC T6
GHG 515 7506 R0001 Ex. Plug, Exde IIC T6Main; 7 pc. E600, P250, P300, P350, P400, P600, W200
Emg; 0 pc.
Main230
1ph
+N
+PE
6016YesS16GHG 511 4306 R3001, SOCKET OUTLET, Exde IIC T6GHG 511 7306 R0001, Ex. Plug, Exde IIC T6Main; 54 pc. E500, E600, P100, P200, P250, P300, P350, P400, P500, P600, Q100, Q250, Q300, Q400, W100, W200, W300
Emg; 0 pc.
UPS230
2ph +PE
6016NoI16GHG 511 4306 R3001, SOCKET OUTLET, Exde IIC T6GHG 511 7306 R0001, Ex. Plug, Exde IIC T610 pc. Q300, W100, W200, W300
Emg690
3ph +PE
60125NoR125GHG 515 4405 R3001, SOCKET OUTLET,
Exde IIC T6
GHG 515 7405 R0001 Ex. Plug, Exde IIC T60 pc.
Main400
3ph
+N
+PE
6063YesS63GHG 514 4506 R3001, SOCKET OUTLET, Exde IIC T6GHG 514 7506 R0001 Ex. Plug, Exde IIC T6Main; 27 pc. E600, P100, P200, P250, P300, P350, P400, P600, Q100, Q300, Q400, W100, W200
Emg; 0 pc.
Emg690
3ph +PE
6063NoR63GHG 514 4405 R3001, SOCKET OUTLET, Exde IIC T6GHG 514 7405 R0001 Ex. Plug, Exde IIC T65 pc. W200, W300
Emg690
3ph +PE
6032NoR32GHG 512 4405 R3001, SOCKET OUTLET, Exde IIC T6GHG 512 7405 R0001 Ex. Plug, Exde IIC T67 pc. Q300, W200, W300

*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power

**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)

Instrument

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
FireNO- kontakt (kontakt=alarm)

2K? i parallel med kontakt / 910? in series med kontakt
Socket:
GHG 591 4201 R0002 6h
Pin 1,2,3
Plug:
GHG 591 2201 R0002 6h
Pin 1,2,3
W100 : 70JBE0071
W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090
W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096
E600 : 70JBE0086
Loss Of PressureNO- kontakt (kontakt=alarm)

2K? i parallel med kontakt / 910? in series med kontakt
Socket:
GHG 591 4201 R0002 6h
Pin 7,8,9
Plug:
GHG 591 2201 R0002 6h
Pin 7,8,9
W100 : 70JBE0071
W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090
W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096
E600 : 70JBE0086
GasNO- kontakt (kontakt=alarm)

2K? i parallel med kontakt / 910? in series med kontakt
Socket:
GHG 591 4201 R0002 6h
Pin 4,5,6
Plug:
GHG 591 2201 R0002 6h
Pin 4,5,6
W100 : 70JBE0071
W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090
W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096
E600 : 70JBE0086
OtherNO- kontakt (kontakt=alarm)

2K? i parallel med kontakt / 910? in series med kontakt
Socket:
GHG 591 4201 R0002 6h
Pin 10,11,12
Plug:
GHG 591 2201 R0002 6h
Pin 10,11,12
W100 : 70JBE0071
W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090
W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096
E600 : 70JBE0086
ESD Battery SystemNO- kontakt (kontakt=alarm)

2K? i parallel med kontakt / 910? in series med kontakt
Socket:
GHG 591 4201 R0002 6h
Pin 13, 14
Plug:
GHG 591 2201 R0002 6h
Pin 13, 14
W100 : 70JBE0071
W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090
W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096
E600 : 70JBE0086

Telecom

Function
Signal type
Connection platform (Description / Type)
Connection temporary equipment (Description / Type)
Area (Module Number / Room Number)
PAAudio, 100V line.Socket:
STAHL 8570/11-404 (yellow)
Plug:
STAHL 8570/12-404 (yellow)
W100, 2 units, W100-US-001
W200, 2 units, W200-US-001
W200, 4 units, US-W200-002-E
W200, 4 units, US-W200-003-E
W300, 4 units, US-W300-001-E
W300, 4 units, US-W300-002-E
W300, 4 units, US-W300-003-E
E600, 2 units, E600-US-001
TelephoneAudioSocket:
STAHL 8570/11-410 (green)
Plug:
STAHL 8570/12-410-S (green)
W100, 1 unit, W100-US-001
W200, 1 unit, W200-US-001
W200, 2 units, US-W200-002-E
W200, 2 units, US-W200-003-E
W300, 2 units, US-W300-001-E
W300, 2 units, US-W300-002-E
W300, 2 units, US-W300-003-E
E600, 1 unit, E600-US-001
Data (Fibre)LC fiber connectorLC fiber connectorW100, 86RBC0003Y, W100-US-001
W200, 86RBC0004Y, W200-US-001
W200, 86RBC0006Y, US-W200-002-E
W200, 86RBC0008Y, US-W200-003-E
W300, 86RBC0012Y, US-W300-001-E
W300, 86RBC0018Y, US-W300-002-E
W300, 86RBC0014Y, US-W300-003-E
E600, 86RBC0017Y, E600-US-001

Utilities

Function
Pressure [bar]
Amount/Flow [max capacity]
Connection - type
Connection - diameter
Connection - material
Area (Module Number / Room Number)
Instrument AirNA
Other
Plant Air7 bar, Dew Point -40deg CelNANABrassAll modules
Sprinkler
Seawater
Freshwater
Drain

Lifting capacity offshore cranes

Crane
1 meter *
2 meter *
3 meter *
1218-73MA001 2 Fall hovedløft: Max 34 tonn på 45,0m radiusMax 34 tonn på 42,5m radiusMax 34 tonn på 40,0m radius
1218-73MA001 3 Fall hovedløft:Max 50 tonn på 35,0m radiusMax 50 tonn på 35,0m radiusMax 50 tonn på 35,0m radius
1218-73MA001 1 Fall hovedløft:Max 17 tonn på 57,5m radiusMax 17 tonn på 55,0m radiusMax 14,9 tonn på 55,0m radius

* Significant waveheight [max. load / max. radius]

Additional information

General kommentar for B&G:
Relene som er inne i brannsentralen i containeren må være NDE, dette fordi at når container mister spenning (singel gas) så skal ikke alarmer aktiveres.


Eksempel på framføring av instrumentsignal i container. Alternative løsninger aksepteres, men signalkontakter og motstander skal være tilkoplet pinnene i støpselet slik som vist 
NB !! Alle 10 motstandene skal inn selv om signalet ikke er i bruk. Dette for å unngå signalfeil-alarm i kontrollrom.


 

Gina Krog_attachm_1.pdf 

Gina Krog_attachm_2.pdf