Power * | Volt [V] | Frequency [Hz] | Phase Current [A] | Neutral Loaded [Yes/No] | System earth ** | Short circuit level min [kA] | Short circuit level max [kA] | Distribution protection fuse [A] | Distribution protection earth fault [mA] | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Main | 690 3ph +PE | 60 | 125 | No | R | 125 | GHG 515 4405 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 515 7405 R0001 Ex. Plug, Exde IIC T6 | 10 pc. W200, W300 | |||
Main | 690 3ph +PE | 60 | 63 | No | R | 63 | GHG 514 4405 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 514 7405 R0001 Ex. Plug, Exde IIC T6 | 13 pc. E600, P250, P300, P350, P400, P600, W100, W200, W300 | |||
Main | 690 3ph +PE | 60 | 32 | No | R | 32 | GHG 512 4405 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 512 7405 R0001 Ex. Plug, Exde IIC T6 | 7 pc. Q300, W200, W300 | |||
Main | 400 3ph +N +PE | 60 | 125 | Yes | S | 125 | GHG 515 4506 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 515 7506 R0001 Ex. Plug, Exde IIC T6 | Main; 7 pc. E600, P250, P300, P350, P400, P600, W200 Emg; 0 pc. | |||
Main | 230 1ph +N +PE | 60 | 16 | Yes | S | 16 | GHG 511 4306 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 511 7306 R0001, Ex. Plug, Exde IIC T6 | Main; 54 pc. E500, E600, P100, P200, P250, P300, P350, P400, P500, P600, Q100, Q250, Q300, Q400, W100, W200, W300 Emg; 0 pc. | |||
UPS | 230 2ph +PE | 60 | 16 | No | I | 16 | GHG 511 4306 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 511 7306 R0001, Ex. Plug, Exde IIC T6 | 10 pc. Q300, W100, W200, W300 | |||
Emg | 690 3ph +PE | 60 | 125 | No | R | 125 | GHG 515 4405 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 515 7405 R0001 Ex. Plug, Exde IIC T6 | 0 pc. | |||
Main | 400 3ph +N +PE | 60 | 63 | Yes | S | 63 | GHG 514 4506 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 514 7506 R0001 Ex. Plug, Exde IIC T6 | Main; 27 pc. E600, P100, P200, P250, P300, P350, P400, P600, Q100, Q300, Q400, W100, W200 Emg; 0 pc. | |||
Emg | 690 3ph +PE | 60 | 63 | No | R | 63 | GHG 514 4405 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 514 7405 R0001 Ex. Plug, Exde IIC T6 | 5 pc. W200, W300 | |||
Emg | 690 3ph +PE | 60 | 32 | No | R | 32 | GHG 512 4405 R3001, SOCKET OUTLET, Exde IIC T6 | GHG 512 7405 R0001 Ex. Plug, Exde IIC T6 | 7 pc. Q300, W200, W300 |
*
Main - Main Power,
Emg - Emergency Power,
Ess - Essential Power,
UPS - UPS Power
**
S = Solidly (direkte jordet),
I = Isolated (isolert)
R = Resistor (resistansjordet)
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
Fire | NO- kontakt (kontakt=alarm) 2K? i parallel med kontakt / 910? in series med kontakt | Socket: GHG 591 4201 R0002 6h Pin 1,2,3 | Plug: GHG 591 2201 R0002 6h Pin 1,2,3 | W100 : 70JBE0071 W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090 W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096 E600 : 70JBE0086 |
Loss Of Pressure | NO- kontakt (kontakt=alarm) 2K? i parallel med kontakt / 910? in series med kontakt | Socket: GHG 591 4201 R0002 6h Pin 7,8,9 | Plug: GHG 591 2201 R0002 6h Pin 7,8,9 | W100 : 70JBE0071 W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090 W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096 E600 : 70JBE0086 |
Gas | NO- kontakt (kontakt=alarm) 2K? i parallel med kontakt / 910? in series med kontakt | Socket: GHG 591 4201 R0002 6h Pin 4,5,6 | Plug: GHG 591 2201 R0002 6h Pin 4,5,6 | W100 : 70JBE0071 W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090 W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096 E600 : 70JBE0086 |
Other | NO- kontakt (kontakt=alarm) 2K? i parallel med kontakt / 910? in series med kontakt | Socket: GHG 591 4201 R0002 6h Pin 10,11,12 | Plug: GHG 591 2201 R0002 6h Pin 10,11,12 | W100 : 70JBE0071 W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090 W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096 E600 : 70JBE0086 |
ESD Battery System | NO- kontakt (kontakt=alarm) 2K? i parallel med kontakt / 910? in series med kontakt | Socket: GHG 591 4201 R0002 6h Pin 13, 14 | Plug: GHG 591 2201 R0002 6h Pin 13, 14 | W100 : 70JBE0071 W200 : 70JBE0073, 0074, 0075, 0087, 0088, 0089, 0090 W300 : 70JBE0076, 0077, 0078, 0091, 0092, 0093, 0094, 0095, 0096 E600 : 70JBE0086 |
Function | Signal type | Connection platform (Description / Type) | Connection temporary equipment (Description / Type) | Area (Module Number / Room Number) |
---|---|---|---|---|
PA | Audio, 100V line. | Socket: STAHL 8570/11-404 (yellow) | Plug: STAHL 8570/12-404 (yellow) | W100, 2 units, W100-US-001 W200, 2 units, W200-US-001 W200, 4 units, US-W200-002-E W200, 4 units, US-W200-003-E W300, 4 units, US-W300-001-E W300, 4 units, US-W300-002-E W300, 4 units, US-W300-003-E E600, 2 units, E600-US-001 |
Telephone | Audio | Socket: STAHL 8570/11-410 (green) | Plug: STAHL 8570/12-410-S (green) | W100, 1 unit, W100-US-001 W200, 1 unit, W200-US-001 W200, 2 units, US-W200-002-E W200, 2 units, US-W200-003-E W300, 2 units, US-W300-001-E W300, 2 units, US-W300-002-E W300, 2 units, US-W300-003-E E600, 1 unit, E600-US-001 |
Data (Fibre) | LC fiber connector | LC fiber connector | W100, 86RBC0003Y, W100-US-001 W200, 86RBC0004Y, W200-US-001 W200, 86RBC0006Y, US-W200-002-E W200, 86RBC0008Y, US-W200-003-E W300, 86RBC0012Y, US-W300-001-E W300, 86RBC0018Y, US-W300-002-E W300, 86RBC0014Y, US-W300-003-E E600, 86RBC0017Y, E600-US-001 |
Function | Pressure [bar] | Amount/Flow [max capacity] | Connection - type | Connection - diameter | Connection - material | Area (Module Number / Room Number) |
---|---|---|---|---|---|---|
Instrument Air | NA | |||||
Other | ||||||
Plant Air | 7 bar, Dew Point -40deg Cel | NA | NA | Brass | All modules | |
Sprinkler | ||||||
Seawater | ||||||
Freshwater | ||||||
Drain |
Crane | 1 meter * | 2 meter * | 3 meter * |
---|---|---|---|
1218-73MA001 2 Fall hovedløft: | Max 34 tonn på 45,0m radius | Max 34 tonn på 42,5m radius | Max 34 tonn på 40,0m radius |
1218-73MA001 3 Fall hovedløft: | Max 50 tonn på 35,0m radius | Max 50 tonn på 35,0m radius | Max 50 tonn på 35,0m radius |
1218-73MA001 1 Fall hovedløft: | Max 17 tonn på 57,5m radius | Max 17 tonn på 55,0m radius | Max 14,9 tonn på 55,0m radius |
* Significant waveheight [max. load / max. radius]
General kommentar for B&G:
Relene som er inne i brannsentralen i containeren må være NDE, dette fordi at når container mister spenning (singel gas) så skal ikke alarmer aktiveres.
Eksempel på framføring av instrumentsignal i container. Alternative løsninger aksepteres, men signalkontakter og motstander skal være tilkoplet pinnene i støpselet slik som vist
NB !! Alle 10 motstandene skal inn selv om signalet ikke er i bruk. Dette for å unngå signalfeil-alarm i kontrollrom.